EasyManua.ls Logo

Tyco T1200-C Series - Page 58

Tyco T1200-C Series
67 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
T1200
MARINEC-P-A
3 02/14
PAGE 58 of 67
Environmental Specification
IP Rating
Designed to IP56
Panel operating
ambient temperature
range
-10
o
C to + 55
o
C
[Batteries 20
o
C to + 50
o
C charge,20
o
C to + 60
o
C discharge]
Storage temperature
range
All panels:-10
o
C to + 70
o
C
Operating and
storage humidity
All panels: 95% Non condensing
Max operational
vibration
GL2003 Section 9
Frequency range: 2Hz to 13.2Hz - amplitude: 1mm [peak]
Frequency range: 13.2Hz to 100Hz acceleration amplitude: 0.7g
EMC
EMC Radiated Immunity:
GL2003 Section 16.
BSEN 50130-4:2011
ESD:
GL 2003 Section 15
BSEN 50130-4:2011
Fast Transient Burst:
GL 2003 Section 17
BSEN 50130-4:2011
Surge:
GL 2003 Section 19
BSEN 50130 -4:2011
Conducted Interference [Low frequency]:
GL 2003 Section 20
Conducted Interference [High frequency]:
GL 2003 Section 18
BSEN 50130-4:2011
Conducted Emissions:
GL 2003 Section 21 [Bridge/Deck areas]
BSEN61000-6-4:2007 + A1:2011
Radiated Emissions:
GL 2003 Section 22 [Bridge/Deck areas]
BSEN61000-6-4:2007 + A1:2011
Salt Mist
LR 1/2002 Section 16
IEC 68-2-11 Test Ka; IEC 68-2-52 Test Kb severity 1