20. Mechanical, Electrical and Environmental Specification 
Mechanical 
Specification 
T1216-C  T1232-C  T1200B-C  T1216R-C  T1232R-C 
Height 
Width 
270 
335 
270 
335 
270 
335 
 
See 
Figure 2 
 
See 
Figure 2 
235 
395 
 
See 
Figure 2 
 
See 
Figure 2 
excluding 
7.1  8.3  8.4  8.1  9.3  4.4  6.7  7.7 
 
Mains Input 
Specification 
AC 
AC 
DC 
AC 
AC 
110  115  70  200  200 
[Warning: Replace 
only with identical 
type & rating of 
BEAB or VDE 
T3.15A 
H250V 
[3.15A anti-surge] 
T3.15A 
H250V 
[3.15A anti-surge] 
T3.15A 
H250V 
[3.15A anti-surge] 
T5A 
H250V 
[5A anti-surge] 
T5A 
H250V 
[5A anti-surge] 
47.5 – 63  47.5 – 63  N/A  47.5 – 63  47.5 – 63 
Minimum of 1mm
2
 c.s.a. copper protected by a 5A fuse. 
 
Output 
T1204A1  T1204A2  T1204DC  T1216-C  T1232-C 
Term Current 
Output 
1.5  1.5  1.5  4  4 
Continuous 
Current 
0.6  0.6  0.6  2  2 
Current 
N/A 
(PSU is integrated into the motherboard)
30  30  30 
Voltage Output, 
Mains On (Vdc) 
27.3 (Nominal, dependent on temperature) 
Output, Mains 
1.5  1.5  1.5  4  4 
28.6 – 20.0  28.6 – 20.0  28.6 – 20.0  28.6 – 20.0  28.6 – 20.0 
load/battery 
disconnected] 
200  200  200  300  300 
Output voltage 
adjustment 
Factory set 
Electronic current limiting 
Outputs not available to user – internally connected to panel PSU monitor. 
Mains failed fault 
output 
Outputs not available to user – internally connected to panel PSU monitor.