22. Appendix 
22.1  EN54 Optional Functions with 
Requirements 
The T1200-C
 
panel has the following EN54 optional 
functions: 
•  Clause 7.8 Outputs to fire alarm devices. 
•  Clause 7.9 Outputs to fire alarm routing 
equipment. 
•  Clause 7.10 Outputs to Fire Protection 
Equipment.  
•  Clause 8.4 Total loss of the power supply. 
•  Clause 8.9 Output to fault warning routing 
equipment. 
•  Clause 10 Test condition. 
22.2  Ancillary Functions Not Required 
By EN54 
The  T1200
 
panel offers several auxiliary functions 
that are not required/allowed by EN54. These are: 
•  Fire  [Routing], Fire Protection and Fault 
[Routing] outputs can be configured to be volt-
free change over contacts. 
•  Detection zones can be configured as non-
latching. 
•  Detection zones can be configured for 
Intrinsically Safe applications. 
•  Class change input - operates sounders briefly 
to signal class changes in educational 
institutions. [Land-based feature]. 
•  Reset relay to interrupt power supplies to 
external equipment that needs to be reset in 
tandem with the T1200-C panel (e.g. IR Beam 
Detectors). 
•  Engineer configurable features: 
o  To require the silencing of the fire alarm 
condition prior to enabling the fire alarm 
condition reset. 
o  To inhibit the operation of the Fire 
Protection Output for a fire condition on a 
zone configured as non-latching. 
o  To inhibit the silencing of fire alarm 
devices and resetting of the fire alarm 
condition for a period of 3 minutes after a 
fire alarm condition occurs. 
o  To prevent fire alarm devices operating 
for any fire alarm condition other than the 
Manual Fire Alarm/Muster condition. 
o  To disable the panel buzzer. 
•  Open collector outputs for Manual Fire 
Alarm/Muster  active, buzzer active, 
disablement active, zonal fire O/Ps for each 
zone up to zone 4. 
•  Remote inputs for remote  Manual Fire 
Alarm/Muster, remote reset and remote silence 
alarms. 
•  One Man Sounder Test [see 16.6]. 
•  Latching fault mode where all fault conditions 
latch until the panel is manually reset. 
•  Restore default configuration of zones and 
outputs. 
•  Selectable options for operation in the Manual 
Fire Alarm or Muster modes. 
•  Muster alarm capable of being initiated, locally 
or from a repeater panel, even if  panel 
processors fail. 
•  Dimmable LEDs on the display.