20
Installation diagram of Steam Home and Commercial
(Fig. 1)
A= Power supply line from electrical distribution board to
steam generator. It is an advantage to install a circuit
breaker between the distribution board and the steam
generator. The circuit breaker must always be switched
on. If the current is switched off before automatic
emptying and flushing of the tank has taken place
(about 70 minutes after bathing is completed), the
operation stops, the tank will not be emptied and the life
of the steam generator will be reduced.
B= Wiring from control panel to steam generator.
C= Thermistor wire
D= Wiring to optional external on/off switch.
E= Steam pipe
F= Drain pipe.
G= Incoming water.
H= The outlet vent must be connected to a ventilation duct
to take the air outdoors.
I= Supply air.
J= Pipe from safety valve.
K= Double swing check valve
Steam room
The steam room must not have any other heat source than
the steam generator. The ambient temperature for the steam
room and steam generator must not exceed 35°C. Any other
sauna adjacent to the steam room must be well insulated
with a minimum of 10 cm ventilated space between them.
Fig. 1
General
IMPORTANT!
• The steam piping must not have any sharp bends.
• Do not direct the steam jet against walls, seats or
other objects. Always keep a space of at least 80
cm clear in front of the steam nozzle.
• There must not be any water pockets in the steam
piping or ventilation ducts. IMPORTANT! There must
not be any kind of blockage in the steam piping (e.g.
taps or valves). The internal diameter of the steam
piping must not be reduced.
• All steam rooms in continuous use for more than two
hours must have an air exchange rate of 10-20 m³ air
per person per hour.
• The power supply for the steam generator must not
be cut off. Therefore avoid installing a power switch,
etc. in the power supply line.
• The drain pipe must have a continuous fall all the
way from the steam generator to the drain.
• The ambient temperature for the steam room and
steam generator must not exceed 35°C.
• The sensor must be located as far from the steam
jet as possible.
• Descale the steam generator regularly in accordance
with the instructions, refer to the heading ”Descaling”.
In areas with hard water, exceeding 4°dH hardness, a
water softener or Tylö MACH 2020 water softener
must be installed
• (Tylö Item no. 9090 8025)
• Clean the steam room regularly
• NB! The steam generator drain must always lead to
a drainage channel outside the steam room. The
steam generator empties its tank 1 hour after each
bath, The water will then be 80-85°C!.
• WARNING! There is a jet of hot steam from the
steam nozzle. Never leave small children
unattended.
• This equipment is not intended to be used by anyone
(including children) with a mental or physical disability
or little experience or knowledge of how to use it,
unless instructed or supervised by someone
responsible for their safety.