EasyManua.ls Logo

UCS C-SV 8A - Smoke Extraction Control

Default Icon
56 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Doc. 85588U - Rev. 22/10/2020
USER MANUALUSER MANUAL
ENEN
Drw. 32367/h18/54
Ifused,theEXTALinputmustbeconnectedtooneofmorenormallyclosedcontacts
(usuallyrelays),putinserieswithoneanother,andwithasingle10kOhmresistorpo-
sionedattheendoftheline.
Ifnotused,theinputmustbeterminatedwitha10kOhmresistor(seediagram6on
page51).
Openingofoneormorecontact(s)(suchasbreakingofthecable)hasthesameeect
aspushingtheemergencybuon.
TheexternalalarminputcanalsobeconnectedtotheNCcontactontheEMSIGoutputforanotherC-SVcontrolunit,ifyou
wantanemergencystatusofthelaertobepropagatedtothecontrolpanelinvolved(seediagram11onpage53).
8.3.1 Emergency
8.3 Commands for smoke extraction
Thecontrolunitcanenterinemergencymodefollowing:
SignalfromaSmokesensor
HoldingtheEmergencyOpenBuon(NCcontact)downforatleast0,5seconds(lteringnecessarytoreducetheriskoffalse
alarms).
ReceivingofanalarmfromanexternalsourceviatheEXTALterminal.Thecontrolunitcanbeconnected,forexample,toan
externalredeteconsystem.
Whenthecontrolunitisinemergencymode,theredLEDstaysonandthemanual,weather,thermostatandCO2sensorfuncons
are disabled. The control unit sends the motors an open command for 3 minutes. If the deadlock” funconisenabled(default
seng),thecommandisrepeatedwith2minutepausesbetweeneachrepeon,foratotalmeof30minutes.
Insolenoidvalvepilongmodethemeschange:thecommandonlylasts3secondsandisrepeatedat10secondintervals,fora
totalmeoftwominutes.
Oncethecondionsthatcausedthealarmcease,thecontrolunitstaysinemergencystatusunlaresetcommandisgiven.
8.3.2 EM SIG
8.3.3 EM CL SIG
8.3.4 AUX SIG
Thisisacleancontactoutputforsignallinganalarmstatusofthecontrolunittoexternalde-
vices.Whenthecontrolunitgoesintoalarmmode(duetoanemergencysignalcomingfrom
smokesensors,theemergencybuon,oranexternalsource),thecontactswitchesasshown
indiagram9onpage52.
Thecontactstaysintheswitchedstateunlthealarmceases,andthecontrolunitisreset.
ItworksexactlylikeEMSIG,butbydefaultitisacvatedonlyintheEMERGENCYCLOSING
status signalling the intervenon of theFireBrigadeorauthorized personnelonEM CL
command.
Ontheotherhand,ifthecontrolunitisconguredinINTERLOCKSLAVEmode(seedip-switch
conguraonpar.8.2),theoutputbehavesasanexactcopyoftheEMSIGoutput,sothatthe
controlunithastwoseparatecleancontactswhichsignaltheemergencystatus.
CleancontactswitchingNCtoNOincaseoffaults.
ON
OFF
ON
OFF
ON
OFF
ON
OFF

Related product manuals