Figure 4-6 AC Input Terminal Block (1-phase)
The mains input terminal blocks can be connected to: 3-phase 400VAC, 1-phase230 VAC or
2-phase 230VAC, see Figure 4-7.
N
L1
L2
L3
PE
PE
N
N/L2
L
L1
PE
PE
PE
PE
6
6
5
5
4
4
3
3
2
2
1
1
1
1
7
7
6 5 4 3 2 1 17
Figure 4-7 AC Connection Options
Recommended AC mains breaker:
400VAC 3-phase: UL listed, triple pole 20A C-characteristic
230VAC 1-phase: UL listed, double pole 40A C-characteristic
4.7 DC Load Connection
Before connecting DC load cables, check the appropriate cable ratings. Maximum cable size
is 9AWG/6.0mm².
1. Check that all the load MCBs are in the OFF position.
2. Connect the negative (-) DC cable to the relevant circuit breaker.