Vision™PLC+HMI Installation Guide
V130-33-TRA22/V130-J-TRA22
V350-35-TRA22/V350-J-TRA22
V430-J-TRA22
Technical Specifications
PLC with Classic panel, Monochrome display 2.4"
PLC with Flat panel, Monochrome display 2.4"
PLC with Classic panel, Color touch display 3.5’’
PLC with Flat panel, Color touch display 3.5’’
PLC with Flat panel, Color touch display 4.3’’
You can find additional information, such as wiring diagrams, in the product’s installation guide
located in the Technical Library at www.unitronics.com.
20.4VDC to 28.8VDC with less than 10% ripple
1. To calculate the actual power consumption, subtract the current for each unused element from the maximum
current consumption value according to the values below:
Relay Outputs
(per output)
All Analog Outputs,
voltage/current
*If the analog outputs are not configured, then subtract the higher value.
High Speed Input. See Note
3
0-5VDC for Logic ‘0’
17-28.8VDC for Logic ‘1’
0-3VDC for Logic ‘0’
20.4-28.8VDC for Logic ‘1’
17-28.8VDC for Logic ‘0’
0-5VDC for Logic ‘1
20.4-28.8VDC for Logic ‘0’
0-3VDC for Logic ‘1
I0, I1: 5.4mA@24VDC
I2-I11: 3.7mA@24VDC
I0, I1: 4.5KΩ
I2-I11: 6.5KΩ
10ms typical, when used as normal digital input