2. V130/V350/V130J/V350J/V430J-TRA22 models comprise a total of 12 inputs.
All 12 inputs may be used as digital inputs. They may be wired in a group via a single jumper
as either npn or pnp.
In addition, according to jumper settings and appropriate wiring:
- Inputs 5 and 6 can function as either digital or analog inputs.
- Input 0 can function as a high-speed counter, as part of a shaft-encoder,
or as normal digital inputs.
- Input 1 can function as either counter reset, normal digital input, or as part of a shaft-encoder.
- If input 0 is set as a high-speed counter (without reset), input 1 can function
as a normal digital input.
- Inputs 7-8 and 9-10 can function as digital, thermocouple, or PT100 inputs; input 11 can also serve as the
CM signal for PT100.
3. If you configure an input as high-speed, you can use an end-device that comprises push-pull drive type.
In this case, the high-speed input voltage ratings for npn/pnp apply.