Vision™PLC+HMI Installation Guide
4. Conversion times are accumulative and depend on the total number of analog inputs configured.
For example, if only one analog input (fast mode) is configured, the conversion time will be 30ms; however,
if two analog (normal mode) and two RTD inputs are configured, the conversion time will be
100ms + 100ms + 300ms + 300ms = 800ms.
5. The analog value can indicate faults as shown below:
Deviates slightly below the input range
Deviates slightly above the input range
Deviates greatly above or below the input range
Temperature coefficient
-200 to 600C/-328 to 1100F. 1 to 320Ω.
300ms minimum per channel. See Note 4 above
Auxillary current for PT100
Up to 50 meters, shielded
6. The analog value can indicate faults as shown below:
Sensor is not connected to input, or value exceeds permissible range
Sensor is short-circuited
100ms minimum per channel. See Note 4 above
Cold junction compensation
Cold junction compensation error
½ hour typically, ±1C/±1.8F repeatability