7. The device can also measure voltage within the range of -5 to 56mV, at a resolution of 0.01mV.
The device can also measure raw value frequency at a resolution of 14-bits (16384). Input ranges are shown
in the following table:
-200 to 1300˚C (-328 to 2372˚F)
200 to 1820˚C (300 to 3276˚F)
0 to 1768˚C (32 to 3214˚F)
-200 to 750˚C (-328 to 1382˚F)
0 to 1768˚C (32 to 3214˚F)
-200 to 760˚C (-328 to 1400˚F)
-200 to 400˚C (-328 to 752˚F)
-200 to 1250˚C (-328 to 2282˚F)
Tyco PCN-124D3MHZ or compatible
Output current
(resistive load)
3A maximum per output
8A maximum total per common
100k operations at maximum load
External precautions required (see Increasing Contact Life Span in the
product’s Installation Guide)
8. Outputs 4, 5, 6, and 7 share a common signal.
Maximum output current
(resistive load)
HSO freq. range with resistive
load
5Hz-200kHz (at maximum load resistance of 1.5kΩ)
9. Outputs 0, 1, 2 and 3 share a common 0V signal.
The 0V signal of the output must be connected to the controller’s 0V.