2 - INTRODUCTION
2.5 Designated Use
• MAC-115, MAC-150 and MAC-205 provide both
central heating and domestic hot water.
• MAH-100, MAH-125 and MAH-165 central heating
only.
• Indoor installation.
• Closet or alcove installation. Direct Vent Boiler does not
require air vents when installed in closet or room.
• Direct vent boiler.
• 
(LP/propane).
2 - Introduction
2.1 Installation shall conform to requirements of authority
having jurisdiction or in absence of such requirements:
UNITED STATES
• National Fuel Gas Code, ANSI Z223.1/NFPA 54
.
• National Electrical Code, NFPA 70.
2.2 Where required by authority having jurisdiction,
installation shall conform to Standard for Controls and Safety
Devices for Automatically Fired Boilers, ANSI/ASME CSD-1.

2.3 Requirements for Commonwealth of
Massachusetts:
Boiler installation must conform to Commonwealth of
Massachusetts code 248 CMR which includes but is not limited
to:

2.6 The unit MUST NOT:
• Directly heat potable water. Indirect heating is
acceptable.
• Heat water with non-hydronic heating system chemicals
present (example, swimming pool water).
• Toxic chemicals, such as those used for boiler
treatment, shall not be introduced into potable water
used for space heating.
• Exceed 43 psig (2.96 bar) maximum system pressure,
or drop below minimum system pressure 7.25 psig (.50
bar)
• Exceed 176°F (80°C) system design temperature.
2.7 Operational Features
• MAH-100 Modulates input to provide CH Turndown
5.6:1
• MAC-115 Modulates input to provide CH Turndown
5.6:1, DHW Turndown 6.9:1
• MAH-125 Modulates input to provide CH Turndown
5.7:1
• MAC-150 Modulates input to provide CH Turndown
5.7:1, DHW Turndown 7:1
• MAH-165 Modulates input to provide CH Turndown
5.5:1
• MAC-205 Modulates input to provide CH Turndown
5.5:1, DHW turndown 7:1
Maximum output available for domestic hot water:
MAC-115 - 105,500 btu/hr (33.8 kW) capable of
providing 2.5 (U.S.) gpm (11.4 liters/min) with a
temperature rise of 70°F/39°C.
MAC-150 - 136,000 btu/h (40 kW), capable of
providing 3.5 (U.S.) gpm (13.2 liters/min) with a
temperature rise of 70°F/39°C.
MAC-205 - 180,000 btu/h (53 kW), capable of
providing 5.0 (U.S.) gpm (18.9 liters/min) with
temperature rise of 70°F/39°C.
• 
• Optional Outdoor Temperature Reset.
• Heat exchanger over heat protection.
• Boiler operating at maximum operating temperature,
providing heat, pressure gauge should not indicate
more than 26.11 psi / 1.80 bar. If reading exceeds this

240013354 REV B [09/15/2021]
2.4 Manufacturer recommends use of Carbon
Monoxide monitor may be requirement of local
jurisdiction.