5.2 Fan cooling
5.2.1
Frames FI9 to FI14
Enough free space must be left around the inverter to ensure sufficient air circulation and cooling.
You will find the required dimensions for free space in the table below.
If several units are mounted on top of each other, the required free space equals 2 * C (see figure
below). Moreover, the outlet air used for cooling by the lower unit must be directed away from the air
intake of the upper unit. When planning the cooling for the space, take into consideration that the
inverter’s heat loss is approx. 2.5% of the nominal capacity.
Type
Dimensions [mm]
A
B
B
2
C
NXI_0168 0300 5
NXI_0125 0208 6
200
20 Min. 300
NXI_0385 0520 5
NXI_0261 0416 6
200
20 Min. 300
NXI_0590 1030 5
NXI_0460 0820 6
200 20 0 Min. 300
NXI_1150 1450 5
NXI_0920 1180 6
200 20 0 Min. 300
NXI_1770 2700 5
NXI_1500 2250 6
The dimensions as per FI13
module
Table 5-1. Mounting space dimensions
Figure 5-7. Installation space.
A
= free space above the inverter
B
= distance between inverter and cabinet wall
B
2
= distance between two inverters
C
= free space underneath of the inverter