7.3.7
Expander board menu (M7)
In the
Expander board menu
the user can 1) see the expander boards connected to the control board
and 2) see and edit the parameters associated with the expander boards.
Go to the next menu level (G#) with
Menu button right
. At this level, you can browse through slots A
to E (see page 52) with the
Browser buttons
to see which expander boards are connected to the
control board. On the lowermost line of the display, you will also see the number of parameters
associated with the board. You can view and edit the parameter values as described in Chapter 7.3.2.
See Table 7-10 and Figure 7-23.
Expander board parameters
P7.1.1.1 AI1 mode 1 5 3
=0…20 mA
=4…20 mA
=0…10 V
=2…10 V
=–10…+10 V
P7.1.1.2 AI2 mode 1 5 1 See P7.1.1.1
P7.1.1.3 AO1 mode 1 4 1
=0…20 mA
=4…20 mA
=0…10 V
=2…10 V
Table 7-10. Expander board parameters (board OPT-A1)