0020261188_00 ecoTEC plus Installation and maintenance instructions 43
Status code Meaning
S.98 Flow/return sensor test running, heating demands are blocked.
S.108 Purging process is running
C Fault messages Overview
Message Possible cause Measure
F.00 Flow temperature sensor
interruption
NTC plug loose/not plugged in Check the NTC plug and plug connection.
NTC sensor defective Replace the NTC sensor.
Multiple plug loose/not plugged
in
Check the multiple plug and plug connection.
Interruption in the cable harness Check the cable harness.
F.01 Return temperature sensor
interruption
NTC plug loose/not plugged in Check the NTC plug and plug connection.
NTC sensor defective Replace the NTC sensor.
Multiple plug loose/not plugged
in
Check the multiple plug and plug connection.
Interruption in the cable harness Check the cable harness.
F.03 Cylinder temperature
sensor interruption
NTC sensor defective Replace the NTC sensor.
NTC plug loose/not plugged in Check the NTC plug and plug connection.
Connection to cylinder electron-
ics defective
Check the connection to the cylinder electronics.
F.10 Flow temperature sensor
short circuit
NTC sensor defective Replace the NTC sensor.
Short circuit in the cable har-
ness
Check the cable harness.
F.11 Return temperature sensor
short circuit
NTC sensor defective Replace the NTC sensor.
Short circuit in the cable har-
ness
Check the cable harness.
F.13 Cylinder temperature
sensor short circuit
NTC sensor defective Replace the NTC sensor.
Short circuit in the cable har-
ness
Check the cable harness.
F.20 Safety shutdown: Safety
cut-out
Flow NTC defective Check the flow NTC.
Return NTC defective Check the return NTC.
Earth connection faulty Check the earth connection.
Stray spark via the ignition
cable, ignition plug or ignition
electrode
Check the ignition cable, ignition plug and ignition electrode.
F.22 Safety shutdown: Water
deficiency
Insufficient/no water in the
product.
Fill the heating installation. ( Page 21)
Interruption in the cable harness Check the cable harness.
F.23 Safety shutdown: Temper-
ature spread too great
Pump blocked Check that the pump is working correctly.
Pump runs with insufficient out-
put
Check that the pump is working correctly.
Flow and return NTC connected
the wrong way round
Check the connection for the flow and return NTC.
F.24 Safety shutdown: Temper-
ature rise too fast
Pump blocked Check that the pump is working correctly.
Pump runs with insufficient out-
put
Check that the pump is working correctly.
Non-return valve blocked Check that the non-return valve is working correctly.
Non-return valve installed incor-
rectly
Check the installation position of the non-return valve.
System pressure too low Check the system pressure.
F.25 Safety shutdown: Flue gas
temperature too high
Flue gas safety cut-out plug is
not plugged in or is loose
Check the plug and the plug connection.
Interruption in the cable harness Check the cable harness.
F.27 Safety shutdown: Flame
simulation
Gas solenoid valve not leak-
tight
Check that the gas solenoid valve works correctly.