Safety 1
0020261188_00 ecoTEC plus Installation and maintenance instructions 5
1.3.11 Risk of poisoning and burns caused
by escaping hot flue gases
Only operate the product if the air/flue pipe
has been completely installed.
With the exception of short periods for
testing purposes, only operate the product
when the front casing is installed and
closed.
1.3.12 Risk of being burned or scalded by
hot components
Only carry out work on these components
once they have cooled down.
1.3.13 Risk of injury due to the heavy
weight of the product
Make sure that the product is transported
by at least two people.
1.3.14 Risk of material damage caused by
using an unsuitable tool
Use the correct tool to tighten or loosen
threaded connections.
1.3.15 Risk of material damage caused by
frost
Do not install the product in rooms prone
to frost.
1.3.16 Risk of corrosion damage due to
unsuitable combustion and room
air
Sprays, solvents, chlorinated cleaning
agents, paint, adhesives, ammonia com-
pounds, dust or similar substances may lead
to corrosion on the product and in the flue
system.
Ensure that the supply of combustion air is
always free of fluorine, chlorine, sulphur,
dust, etc.
Ensure that no chemical substances are
stored at the installation site.
If you are installing the product in
hairdressing salons, painter's or joiner's
workshops, cleaning businesses or similar
locations, choose a separate installation
room in which the room air is technically
free of chemical substances.
Ensure that the combustion air is not
routed through chimneys which have
previously been used with floor-standing
oil-fired boilers, or with other boilers,
which could cause soot to build up in the
chimney.
1.3.17 Risk of material damage caused by
leak detection sprays and liquids
Leak detection sprays and liquids block the
filter of the mass flow sensor on the Venturi,
and thus destroy the mass flow sensor.
During repair work, do not apply any leak
detection sprays or liquids to the covering
cap on the filter of the Venturi.
1.3.18 Risk of damage to the flexible gas
pipe
The corrugated gas pipe may become dam-
aged if weight is placed on it.
Do not suspend the compact thermal
module on the flexible gas pipe, for
example during maintenance work.
1.4 Regulations (directives, laws,
standards)
Observe the national regulations, stand-
ards, guidelines and laws.

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Vaillant ecoTEC plus VC 406/5-5 and is the answer not in the manual?

Vaillant ecoTEC plus VC 406/5-5 Specifications

General IconGeneral
BrandVaillant
ModelecoTEC plus VC 406/5-5
CategoryBoiler
LanguageEnglish

Related product manuals