54 Installation and maintenance instructions ecoTEC plus 0020261188_00
VC 476/5-5 (E-DE) VC 476/5-5 (LL-DE)
Effective output range (P) at 50/30 °C
8.7 48.0 kW 8.7 48.0 kW
Effective output range (P) at 80/60 °C
7.8 44.1 kW 7.8 44.1 kW
Maximum heat input heating (Q max.)
45.2 kW 45.2 kW
Minimum heat input heating (Q min.)
8.1 kW 8.1 kW
VC 636/5-5 (E-DE) VC 636/5-5 (LL-DE)
Effective output range (P) at 50/30 °C
12.2 63.5 kW 12.2 63.5 kW
Effective output range (P) at 80/60 °C
11.0 58.7 kW 11.0 58.7 kW
Maximum heat input heating (Q max.)
60.0 kW 60.0 kW
Minimum heat input heating (Q min.)
11.3 kW 11.3 kW
Technical data Power/load (G31)
VC 406/5-5 (E-DE) VC 406/5-5 (LL-DE)
Effective output range (P) at 50/30 °C
8.6 39.5 kW 8.6 39.5 kW
Effective output range (P) at 80/60 °C
7.8 37.1 kW 7.8 37.1 kW
Maximum heat input heating (Q max.)
38.0 kW 38.0 kW
Minimum heat input heating (Q min.)
8.1 kW 8.1 kW
VC 476/5-5 (E-DE) VC 476/5-5 (LL-DE)
Effective output range (P) at 50/30 °C
8.6 46.6 kW 8.6 46.6 kW
Effective output range (P) at 80/60 °C
7.8 44.0 kW 7.8 44.0 kW
Maximum heat input heating (Q max.)
45.2 kW 45.2 kW
Minimum heat input heating (Q min.)
8.1 kW 8.1 kW
VC 636/5-5 (E-DE) VC 636/5-5 (LL-DE)
Effective output range (P) at 50/30 °C
12.0 62.1 kW 12.0 62.1 kW
Effective output range (P) at 80/60 °C
11.1 58.4 kW 11.1 58.4 kW
Maximum heat input heating (Q max.)
60.0 kW 60.0 kW
Minimum heat input heating (Q min.)
11.3 kW 11.3 kW
Technical data General
VC 406/5-5 (E-DE) VC 406/5-5 (LL-DE)
Gas category
II2ELL3P, I2E II2ELL3P
Diameter of the gas pipe at the product outlet
25 mm 25 mm
Diameter at the outlet of the gas compression fitting, outside thread
1" 1"
Diameter of the heating pipe at the product outlet, outside thread
1 1/2" 1 1/2"
Diameter at the outlet of the heating connection, outside thread
1 1/2" 1 1/2"
Connection diameter of the expansion relief valve, inside thread
3/4" 3/4"
G20 gas supply pressure
2.0 kPa
(20.0 mbar)
G25 gas supply pressure
2.0 kPa
(20.0 mbar)
2.0 kPa
(20.0 mbar)
G31 gas supply pressure
5.0 kPa
(50.0 mbar)
5.0 kPa
(50.0 mbar)
CE number (PIN)
CE-0063CS3428 CE-0063CS3428
Smoke mass flow in heating mode at P min.
3.9 g/s 3.9 g/s
Smoke mass flow in heating mode at P max.
17.0 g/s 17.1 g/s
Released system types
C13x, C33x, C43x, C53x,
C93x, B23x, B23(P)x, B33x,
B53x, B53(P)x
C13x, C33x, C43x, C53x,
C93x, B23x, B23(P)x, B33x,
B53x, B53(P)x
Flue gas temperature in heating mode (50/30 °C) at P min.
37 37
Flue gas temperature in heating mode at P max. 50/30 °C
53 53
Flue gas temperature in heating mode (80/60 °C) at P min.
61 61