Co-Axial Venting
Horizontal Vent Termination Location
The vent terminal must be located on an outside
wall or through the roof.
This direct vent appliance is designed to operate
when an undisturbed airȵ ow hits the outside vent
terminal from any direction.
The minimum clearances from this terminal that
must be maintained when located on an outside
wall are shown in ȴ gure below. Any reduction in
these clearances could result in a disruption of the
KEY
VENT TERMINAL LOCATIONS - MINIMUM DISTANCES
Measured from the center of vent
MINIMUM
CLEARANCE
Inches Cm
A Clearance above grade, verandah, porch, deck or balcony 12 30
B Clearance to window or door that may be opened 12 30
C Clearance to permanently closed window (recommended to prevent condensation on window) 12 30
D
Vertical clearance to ventilated soɝ t located above the terminal within a horizontal distance of 2 feet (60 cm)
from the center-line of the terminal
18 46
E Clearance to unventilated soɝ t 12 30
F Clearance to outside corner 12 30
G Clearance to inside corner 12 30
H
Horizontal clearance to center-line of meter/regulator assembly located within 15 feet (4.6bm) below the
terminal
36 90
I
Clearance to service regulator vent outlet
36 90
J Clearance to non-mechanical air supply inlet to the building or the combustion air inlet to any other appliance 12 30
K Clearance to a mechanical air supply inlet 72 180
L
Clearance above paved sidewalk or a paved driveway located on public property
Note: A vent must not terminate directly above a sidewalk or paved driveway, which is located between two single-
family dwellings and serves both dwellings. THIS DOES NOT APPLY to direct vent, non-consdensing appliances in
the Province of Ontario.
84 210
M
Clearance under a verandah, porch, deck or balcony
Only permitted if veranda, porch, deck or balcony is fully open on a minimum of 2 sides beneath the ȵ oor
12 30
Note: Local codes and regulations may require di΍ erent clearances.
V
G
A
Min. 72”
Max. 72”
Alcove detail
(open on one
side) Normal
ceiling/soɝ t
clearances
apply.
airȵ ow or a safety hazard. Local codes or regulations
may require greater clearances.
The vent terminal must not be recessed into a wall
or siding.
The vent terminal should be positioned where any
snowdrifts will not cover it.
Sidewall vent terminations require a terminal guard
such as 658TG or 845TG when accessiblewithin 7
of ground.