EasyManua.ls Logo

VAT 61232-KEGJ-0002 - User Manual

VAT 61232-KEGJ-0002
69 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
Loading...
Installation, Operating & Maintenance Instructions
Series 612 DN 40 (I.D. 1.5”), RS485
VAT Vakuumventile AG, CH-9469 Haag, Switzerland
Tel +41 81 771 61 61 Fax +41 81 771 48 30 CH@vatvalve.com www.vatvalve.com
289917EA
2011-07-07
1/69
Butterfly Pressure Control Valve
with RS485 interface
This manual is valid for the valve ordering number(s):
61232-KEGJ-0002
configured with firmware 612P.1E.65
The fabrication number is indicated on each product as per the label
below (or similar):
made in Switzerland
Fabrication No.:
612
. .
. . . .
. . . . / . . . .
. . . . . .
Fabrication number
sample picture
Explanation of symbols:
Read declaration carefully before you start any other
action!
Keep body parts and objects away from the valve
opening!
Attention!
Hot surfaces; do not touch!
Loaded springs and/or air cushions are potential
hazards!
Wear gloves!
Disconnect electrical power and compressed air
lines. Do not touch parts under voltage!
Read these «Installation, Operating & Maintenance Instructions» and the enclosed «General
Safety Instructions» carefully before you start any other action!

Questions and Answers

  • J
    John HuntAug 31, 2025
    Why pressure reading is wrong on VAT Control Unit?
    • J
      Jonathan MitchellAug 31, 2025
      To fix a pressure reading that is wrong or negative on your VAT Control Unit, check the electrical connections, verify the valve version and configuration, perform ZERO after reaching base pressure, and verify the sensor supply voltage. The issue may stem from unconnected sensors, an incorrect sensor version, an unperformed ZERO, or insufficient sensor power.
  • S
    Samuel JohnsonAug 25, 2025
    Why is the VAT 61232-KEGJ-0002 Control Unit pressure reading wrong or negative?
    • B
      Bruce ColemanAug 25, 2025
      If the pressure reading on your VAT Control Unit is incorrect or negative, check the sensor connections according to the electrical connection guidelines. For a 2-sensor version, verify the configuration. Perform ZERO after reaching the base pressure, and ensure the sensor power supply provides sufficient power.
  • B
    banksdavidSep 15, 2025
    What to do if the Network Status LED is off (Device is not on line) on my VAT 61232-KEGJ-0002 Control Unit?
    • P
      Paul HernandezSep 15, 2025
      Connect the valve to DeviceNet® according to the «DeviceNet® connection» instructions and ensure that power is provided.
  • E
    Elizabeth RamirezSep 23, 2025
    What to do if the VAT 61232-KEGJ-0002 Control Unit CLOSE VALVE does not work?
    • R
      rschwartzSep 23, 2025
      If the VAT Control Unit CLOSE VALVE function does not work, it could be because the safety mode is active (check for D on the display) or maintenance mode is active. Provide power to the motor to allow for operation; refer to «Electrical connection» for details. Also, refer to “Display shows «M C»”.
  • M
    mendezkevinSep 10, 2025
    Why does ZERO not work on my VAT 61232-KEGJ-0002?
    • C
      codygonzalezSep 10, 2025
      If the VAT Control Unit ZERO does not work, OPEN the VALVE and bring the chamber to base pressure before performing ZERO. If ZERO is disabled, enable it, referring to «Valve configuration» for details.
  • M
    mccoymarkSep 23, 2025
    What to do if the VAT 61232-KEGJ-0002 display shows «E 20» (fatal error - limit stop of valve unit not detected)?
    • M
      Margaret GrahamSep 23, 2025
      If the VAT Control Unit display shows «E 20», it indicates a fatal error where the limit stop of the valve unit is not detected. This could be due to a clamp coupling screw that is not fastened. Tighten the screw, referring to chapter «Maintenance» for details.
  • A
    Amanda WoodAug 29, 2025
    Why PRESSURE CONTROL does not work on VAT 61232-KEGJ-0002?
    • K
      Kimberly RodriguezAug 29, 2025
      To resolve the issue of PRESSURE CONTROL not working on your VAT Control Unit, ensure that power is supplied to the motor. Select PRESSURE CONTROL mode and perform LEARN. The problem may be due to safety mode being active, PRESSURE CONTROL not being selected, or LEARN not being completed.
  • E
    Erica HaleySep 18, 2025
    What should I do if the OPEN VALVE function does not work on my VAT Control Unit?
    • X
      xsmithSep 18, 2025
      If the OPEN VALVE function isn't working, check if safety mode is active, indicated by a 'D' on the display. If so, provide power to the motor. Also, check if maintenance mode is active. Refer to «Electrical connection» for details. You can also refer to the section “Display shows «M100»”.
  • A
    ashley10Sep 22, 2025
    What to do if there are no dots lighted on the VAT 61232-KEGJ-0002 Control Unit display?
    • A
      amy21Sep 22, 2025
      Connect the valve to the power supply according to «Electrical connection» and ensure that the power supply is working.
  • V
    Virginia GallegosAug 27, 2025
    What does error E21 mean on VAT 61232-KEGJ-0002 display?
    • C
      Christopher AcostaAug 27, 2025
      If your VAT Control Unit displays 'E 21' and the position '009999' (fatal error - rotation angle of valve plate limited during power up), check if the valve plate is centric adjusted, if the valve unit is heavily contaminated or if the valve plate is mechanically obstructed. Adjust the valve plate according to the maintenance procedure, clean the valve unit, and resolve any obstructions. Reset the control unit by cycling the power off and on, or send a reset command locally via the service port with CV/CPA/Service Box2.

VAT 61232-KEGJ-0002 Specifications

General IconGeneral
BrandVAT
Model61232-KEGJ-0002
CategoryControl Unit
LanguageEnglish

Related product manuals