5-7
5 Warning and Alarm Messages
Displayed Alarm Messages
Short Alarm A short has occurred in the sensor
wiring or in the sensor.
Call for service following the proce-
dures established for your site.
Water Out Alarm Water level is below the float switch
making the groundwater sensor inef-
fective.
Call for service following the proce-
dures established for your site.
Table 5-7.- Type A Sensor Alarms
Alarm Cause Action
Fuel Alarm Fuel is present in the area being mon-
itored by the sensor.
Call for service following the proce-
dures established for your site.
Out Alarm The sensor setup was performed
incorrectly or a sensor is discon-
nected or is not functioning properly.
Call for service following the proce-
dures established for your site.
Short Alarm A short has occurred in the sensor
wiring or in the sensor.
Call for service following the proce-
dures established for your site.
Setup Data Warning Device setup data problem. Recheck device setup parameters.
Water Alarm Water is present in the area being
monitored by the sensor.
Call for service following the proce-
dures established for your site.
Table 5-8.- Type B Sensor Alarms
Alarm Cause Action
Fuel Alarm Fuel is present in the area being mon-
itored by the sensor.
Call for service following the proce-
dures established for your site.
High Liquid Alarm The sensor detects a high liquid level. Call for service following the proce-
dures established for your site.
Liquid Warning Liquid reached 1 inch (25.4 mm) on
the dispenser pan or containment
sump sensors.
Immediately follow the alarm report-
ing procedures established for your
site.
Out Alarm The sensor setup was performed
incorrectly or a sensor is discon-
nected or is not functioning properly.
Call for service following the proce-
dures established for your site.
Setup Data Warning Device setup data problem. Recheck device setup parameters.
Short Alarm A short has occurred in the sensor
wiring or in the sensor.
Call for service following the proce-
dures established for your site.
Table 5-6.- Groundwater Sensor Alarms
Alarm Cause Action

Table of Contents

Other manuals for Veeder-Root TLS-450

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Veeder-Root TLS-450 and is the answer not in the manual?

Veeder-Root TLS-450 Specifications

General IconGeneral
BrandVeeder-Root
ModelTLS-450
CategoryMusic Mixer
LanguageEnglish

Related product manuals