10 CSLD Troubleshooting
Actual CSLD Test Problems Analyzed
10-22
Analysis
The moving average table shows erratic probe readings. Fluid is rising and falling by several gallons.
Solution
Replace probe.
CSLD PROBLEM 5 - TANK 1 IS FAILING
Reports I251, I201, IA52, IA51, and I609 were collected for analysis.
Diagnostics
I25100
JUN 26, 1996 2:37
STATION
HEADER
INFO
PHONE
CSLD TEST RESULTS
TANK PRODUCT RESULT
1 UNLEADED PER: JUN 24, 1996 FAIL
2 UNLEADED PLUS PER: JUN 26, 1996 PASS
3 SUPER UNLEADED PER: JUN 26, 1996 PASS
4 KEROSENE PER: JUN 26, 1996 PASS
5 DIESEL PER: JUN 26, 1996 PASS
I20100
STATION HEADER INFO
JUN 26, 1996 2:36 PM
TANK PRODUCT VOLUME TLC VOLUME ULLAGE HEIGHT WATER TEMP
1 UNLEADED 8627 8617 3000 63.42 0.0 76.9
2 UNLEADED PLUS 9286 9278 2341 67.92 0.0 72.2
3 SUPER UNLEADED 8315 8309 3312 61.38 0.0 70.6
4 KEROSENE 5399 5395 598 60.21 0.0 70.9
5 DIESEL 2989 2987 2940 46.27 0.0 70.1
IA5200
JUN 26, 1996 2:37 PM
CSLD DIAGNOSTICS: RATE TEST
TK DATE LRATE INTVL ST AVLRTE VOL C1 C3 FDBK ACPT THPUT EVAP RJT
1 9606240446 -0.270 10.3 2 -0.217 6406 21 20 0.0 0.0 44.32 0.000 1