5-10
5 Warning and Alarm Messages
Displayed Alarm Messages
Table 5-12.- Line Pressure Sensor Alarms
Alarm Cause Action
Communication Alarm Console has lost communication with the relay. Call for service following the proce-
dures established for your site.
Setup Data Warning Device setup data problem. Recheck device setup parameters.
Table 5-13.- Printer Alarms
Alarm Cause Action
Printer Error Printer feed roller release is open. Push the release lever to the up posi-
tion.
Printer out of Paper Paper roll is empty. Replace the paper roll with Veeder-
Root part number 514100-456 only.
Table 5-14.- Pump Alarms
Alarm Cause Action
Pump Out Alarm Hardware failure or setup data warning on depen-
dent device (Relay or External Input) prevents this
device from working.
Call for service following the proce-
dures established for your site.
Setup Data Warning Device setup data problem. Recheck device setup parameters.
Table 5-15.- Line Alarms
Alarm Cause Action
Line Out Alarm Hardware failure or setup data warning on
dependent device (Pump) prevents this device
from working.
Call for service following the proce-
dures established for your site.
Line Setup Data Warning Device setup data problem. Recheck device setup parameters.
Table 5-16.- Communication Alarms
Alarm Cause Action
Setup Data Alarm Hardware failure or setup data warning on depen-
dent device (Pump) prevents this device from
working.
Call for service following the proce-
dures established for your site.
Setup Data Warning Device setup data problem. Recheck device setup parameters.