EasyManua.ls Logo

Vega VEGAFLEX 82 - Installation Position and Vessel Type

Vega VEGAFLEX 82
96 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
14
4 Mounting
VEGAFLEX 82 • 4 … 20 mA/HART - two-wire
44222-EN-170220
Youcannddetailedinformationontheprocessconditionsinchapter
"Technicaldata" as well as on the type label.
4.2 Mounting instructions
Mount VEGAFLEX 82 in such a way that the distance to vessel instal-
lations or to the vessel wall is at least 300 mm (12 in). In non-metallic
vessels, the distance to the vessel wall should be at least 500 mm
(19.7 in).
During operation, the probe must not touch any installations or the
vessel wall. If necessary, fasten the probe end.
In vessels with conical bottom it can be advantageous to mount the
sensor in the center of the vessel, as measurement is then possible
nearly down to the lowest point of the bottom. Keep in mind that
measurement all the way down to the tip of the probe may not be pos-
sible. The exact value of the min. distance (lower dead band) is stated
in chapter "
Technicaldata".
Fig. 2: Vessel with conical bottom
Plastic vessel/Glass vessel
The guided microwave principle requires a metallic surface on the
processtting.Therefore,inplasticvessels,etc.,useaninstru-
mentversionwithange(fromDN50)orplaceametalsheet
(ø>200mm/8in)beneaththeprocessttingwhenscrewingitin.
Makesurethattheplatehasdirectcontactwiththeprocesstting.
When using the probes without metal vessel wall, e.g. in plastic
vessels,themeasuredvaluecanbeinuencedbystrongelectromag-
neticelds(emittedinterferenceaccordingtoEN61326:classA).
Use a probe in coax version for applications in liquids.
Installation position
Type of vessel

Table of Contents

Other manuals for Vega VEGAFLEX 82

Related product manuals