79
11 Supplement
VEGAPULS 62 • Probus PA
36505-EN-181127
Recommended measuring range
Ʋ Antenna ø 40 mm (1.575 in) up to 15 m (49.21 ft)
Ʋ Antenna ø 48 mm (1.89 in) up to 20 m (65.62 ft)
Ʋ Antenna ø 75 mm (2.953 in) up to 40 m (131.23 ft)
Ʋ Antenna ø 95 mm (3.74 in) up to 50 m (164 ft)
Ʋ Parabolic antenna up to 75 m (246.1 ft)
Output variable
Output signal digital output signal, format according to IEEE-754
Sensor address 126 (default setting)
Damping (63 % of the input variable) 0 … 999 s, adjustable
Probus PA prole 3.02
Number of FBs with AI (function blocks
with analogue input)
3
Default values
Ʋ 1. FB Primary Value (lling height linearized in %)
Ʋ 2. FB Secondary Value 1 (lling height in %)
Ʋ 3. FB Secondary Value 2 (distance value)
Current value
Ʋ Non-Ex and Ex ia instrument 10 mA, ±0.5 mA
Ʋ Ex-d-ia instruments 16 mA, ±0.5 mA
Resolution, digital < 1 mm (0.039 in)
Deviation (according to DIN EN 60770-1)
Process reference conditions according to DIN EN 61298-1
Ʋ Temperature +18 … +30 °C (+64 … +86 °F)
Ʋ Relative humidity 45 … 75 %
Ʋ Air pressure 860 … 1060 mbar/86 … 106 kPa (12.5 … 15.4 psig)
Installation reference conditions
Ʋ Min. distance to internal installations > 200 mm (7.874 in)
Ʋ Reector Flat plate reector
Ʋ False reections Biggest false signal, 20 dB smaller than the useful signal
Deviation with liquids ≤ 2 mm (meas. distance > 0.5 m/1.64 ft)
Non-repeatability
2)
≤ 1 mm
Deviation with bulk solids The values depend to a great extent on the application.
Binding specications are thus not possible.
Deviation with bulk solids The values depend to a great extent on the application.
Binding specications are thus not possible.
2)
Already included in the meas. deviation