85
11 Supplement
VEGAPULS 62 • Probus PA
36505-EN-181127
Integrated clock
Date format Day.Month.Year
Time format 12 h/24 h
Time zone, factory setting CET
Max. rate deviation 10.5 min/year
Additional output parameter - Electronics temperature
Range -40 … +85 °C (-40 … +185 °F)
Resolution < 0.1 K
Deviation ±3 K
Output of the temperature values
Ʋ Indication Via the display and adjustment module
Ʋ Analogue Via the current output, the additional current output
Ʋ Digital Via the digital output signal (depending on the electron-
ics version)
Voltage supply
Operating voltage U
B
Ʋ Non-Ex instrument 9 … 32 V DC
Ʋ Ex-ia instrument - Power supply
FISCO model
9 … 17.5 V DC
Ʋ Ex-ia instrument - Power supply
ENTITY model
9 … 24 V DC
Ʋ Ex-d-ia instrument 16 … 32 V DC
Operating voltage U
B
- illuminated display and adjustment module
Ʋ Non-Ex instrument 13.5 … 32 V DC
Ʋ Ex-ia instrument - Power supply
FISCO model
13.5 … 17.5 V DC
Ʋ Ex-ia instrument - Power supply
ENTITY model
13.5 … 24 V DC
Ʋ Ex-d-ia instrument No lighting possible (integrated ia barrier)
Number of sensors per DP/PA segment coupler, max.
Ʋ Non-Ex 32
Ʋ Ex 10
Potential connections and electrical separating measures in the instrument
Electronics Not non-oating
Reference voltage
8)
500 V AC
Conductive connection Between ground terminal and metallic process tting
Overvoltage protection
Highest continuous operating voltage 35 V DC
8)
Galvanic separation between electronics and metal housing parts