6 Set up with the display and adjustment module
VEGAPULS 6X • Modbus and Levelmaster protocol
1015562-EN-240311
Conrmifthetwocharacterstringsareidentical.Thevericationtexts
are provided in German and in the case of all other menu languages,
in English.
Afterwardsyouconrmthattheserialnumberofyourinstrumentwas
carried over correctly. This is used to check device communication.
In the next step, the instrument checks the data of the measurement
and decides by means of the evaluation results if a functions test
is required. If a function test is necessary, the following message is
displayed.
In this case, you have to carry out a function test.
Function test:
During a function test, you have to test the safety function of the
instrument in the vessel with the original medium.
Youcanndthedetailedsequenceofthefunctiontestinchapter
"Functionalsafety(SIL)" of the operating instructions.
Verify parameter:
Allsafety-relevantparametersmustbeveriedafterachange.After
thefunctiontest,allmodied,safety-relevantparameterswillbe
listed.Conrmthemodiedvaluesoneaftertheother.
If the described process of parameter adjustment was run through
completely and correctly, the instrument will be locked and hence
ready for operation.
Otherwise the instrument remains in the released and hence unsafe
condition.
Note:
When the adjustment is blocked, the adjustment via other systems is
also blocked.