17
6 Set up with the display and adjustment module
VEGAPULS 6X • Modbus and Levelmaster protocol
1015562-EN-240311
4. Move with [ESC] and [->] to the min. adjustment
Proceed as follows:
1. Select with [->] the menu item "DistanceB(min.value)" and
conrmwith[OK].
2. Edit the distance value with [OK] and set the cursor to the re-
quested position with [->].
3. Set the requested distance value for 0 % (e.g. distance from the
sensor up to the vessel bottom) with [+] and save with [OK]. The
cursor now jumps to the distance value.
6.2.3 Reset
During a reset, parameter settings made by the user are reset to the
valuesofthefactorysettings.Youcannedthevaluesinchapter
"Menu overview".
Information:
The language and Bluetooth access code are not reset, a currently
running simulation however is aborted.
Reset - Factory settings:
•
Restoringthefactoryandorder-specicparametersettings
•
Resetting a user-set measuring range to the recommended meas-
uring range (see chapter "Technical data")
•
Deleting a created false signal suppression, a user-programmable
linearisation curve as well as the measured value and echo curve
memory
4)
Reset - Restart:
Isusedtorestartthedevicewithoutswitchingotheoperatingvolt-
age.
Distance B (min. value)
Reset
4)
The event and parameter change memories are maintained.