58
PHTM II
Installation, Operating & Service Instructions
110331-01 - 5/20
16 Operation (continued)
Table 16-12: Menu
FrFr (visible only after password entered, continued)
Default
Range/
Choices
Parameter and Description
0% 0 - 30%
F06F06 Minimum Modulation Capacity
Increases lowest modulation rate during any call for heat.
0% -9% to +8%
F07F07 Gas Valve Ignition Capacity
Increases or decreases gas valve position during burner ignition. For example,
increasing this value causes gas valve to be more open (more fuel) during ignition.
0% -16% to 14%
F08F08 Blower Ignition Capacity
Increases or decreases blower speed during burner ignition. For example, increasing this
value causes the blower speed to be higher (more air) during ignition.
Table 16-13: Menu
5P5P (visible only after password entered)
Default
Range/
Choices
Parameter and Description
0 0, 1
501501 Temperature Units
Sets display temperature in degrees Fahrenheit or Celsius.
(0) Fahrenheit
(1) Celsius
60
0 to 120
(minutes)
502502 DHW Priority Time
When DHW Priority Time is greater than zero and DHW heat demand is present, DHW
demand has priority over heating demands for this specified time. After DHW demand
ends or DHW Priority Time is exceeded; and CH demand is present, CH demand has
priority over DHW demand.
130°F
54°C
-50 to 180°F
(10°C to
83°C)
506506 Central Heat 1 Min Boiler Water Temp
Sets a low limit for Reset setpoint. Set this parameter to lowest supply water temperature
that will provide enough heat for type of radiation used to function properly. Always
consider type of radiation when adjusting this parameter.
130°F
54°C
-50 to 180°F
(10°C to
83°C)
510510 Central Heat 2 Min Boiler Water Temp
Sets a low limit for Reset setpoint. Set this parameter to lowest supply water temperature
that will provide enough heat for type radiation used to function properly. Always consider
type of radiation when adjusting this parameter.
0 0, 1, 2
511511 Auxiliary Thermostat Input Select:
May be used as "Recirculation Enable", "Indirect Water Heater (IWH) DHW demand"
(heating boilers only) or "CH Zone 2 Heat demand" input.
(0) Recirculation Enable Recirculation enable input. When Comfort Mode is enabled,
"Aux Pump" output is energized to run a recirculation pump
when this input is "On". This input may be (a) jumpered
allowing recirculation pump to run at all times, (b) wired to a
time of day clock, or (c) wired to a momentary pushbutton.
Note: recirculation pump continues to run for 15 minutes
after this input is removed.
(1) DHW Demand Indirect Water Heater (IHW) DHW heat demand. (Heating
Boiler Only)
(2) CH Zone 2 Thermostat CH2 heat demand.