26 Appendix 1 Technical And Engineering Data
NetSure 731 A41 Subrack Power System User Manual
Appendix 1 Technical And Engineering Data
Table 1 Technical data
-5℃~+40℃(derating is necessary above 40°C)
≤2000m(derating is necessary above 2,000m)
No conductive dust or erosive gases. No possibility of explosion
Input AC voltage
frequency
≤74A(including 10A AC output current);
≤84A(using R48-3500e3 modules)
-53.5Vdc(If it is used for outdoor,the rated voltage is-54V)
DC load output ≤150A (R48-3000e3/R48-3000A3)
DC load output ≤185A (R48-3500e3)
battery charging current≤56A
Note: in 45℃, full load output, above 45℃, the power derating 2% per ℃.
Voltage set-point
accuracy
Noise (peak-peak) (rated
output)
Weighted noise (rated
output)
AC input alarm and
protection
AC input over-voltage
alarm point
Default: 280 ± 5Vac, configurable through controller
AC input over-voltage
alarm recovery point
Default: 270 ± 5Vac, 10Vac lower than the AC input over-voltage alarm point
AC input under-voltage
alarm point
Default: 180 ± 5Vac, configurable through controller
AC input under-voltage
alarm recovery point
Default: 190 ± 5Vac, 10Vac higher than the AC input under-voltage alarm point
AC input over-voltage
protection point
305 ± 5Vac by default, configurable through controller
AC input over-voltage
protection recovery point
295 ± 5Vac by default, 10Vac lower than the AC input over-voltage alarm point
AC input under-voltage
protection point
Default: 80 ± 5Vac, configurable through controller
AC input under-voltage
protection recovery point
Default: 95 ± 5Vac, 10Vac higher than the AC input under-voltage alarm point
DC output alarm and
protection
DC output over-voltage
alarm point
Default: -58.0 ± 0.2Vdc, configurable through controller
DC output over-voltage
recovery point
Default: -57.5 ± 0.2Vdc, 0.5Vdc lower than the over-voltage alarm point
Default: -45.0 ± 0.2Vdc, configurable through controller