EasyManua.ls Logo

Vertiv Liebert CRV CRD100-0D00A - 7.2 Routine Maintenance and Inspection (Semi- annually)

Vertiv Liebert CRV CRD100-0D00A
126 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Maintenance & Troubleshooting
Vertiv | Liebert CRD10 | User Manual 90
7.2 Routine Maintenance and Inspection (Semi- annually)
Following is the checklist (refer Table 7-2) of the items and functions that need to be checked semi-annually
to ensure a smooth operational flow and check the functionality as well as the wear-and-tear of the
components in the Liebert CRD 10kW range of air conditioners.
Table 7-2 Routine Maintenance & Inspection (Semi-annually)
Components
Item
Remark
Air Filter
Check for clogging or damage
Check the filter clogging switch
Clean the filter
Fan
The fan blades are not distorted
The bearings are not worn out
Check and fasten the circuit connections
Compressor
Check for leakage
Listen to the operation sound, observe the operation vibration
Check and fasten the circuit connections
Air-cooled
condenser
Check the fins cleanness
The fan base should be firm
The fan vibration absorber is not deteriorated or damaged
Check the voltage regulating function of the rotation speed controller
The temperature switch is set at the required position
The refrigerant pipes are properly supported
Check and fasten the circuit connections
Check the suction pressure

Table of Contents

Related product manuals