Installation
Vertiv | Liebert CRD10 | User Manual 24
2.7 Operating and Storage Environment Conditions
In this section, take a look at the environmental conditions including the Operating and Storage environment.
2.7.1
Operating Condition
Table 2-4 defines the operating condition parameters including the ambient temperature, protection level,
altitude and voltage range.
Table 2-4 Operating Parameters
Indoor: Temperature 18°C (64.4F) to 40°C (104F), Relative humidity 17% to 60%
Outdoor: Temperature -15°C (5°F ) to 45°C (113°F) without Low Ambient Kit
Temperature -34°C (-29.2°F ) to 45°C (113°F) with Low Ambient Kit
Indoor Unit: IP20, Outdoor Unit: IPX4
< 2000m(6561.6ft.). Above that, please contact Vertiv
2.7.2
Storage Condition
Table 2-5 defines the Storage condition parameters including the ambient humidity, ambient temperature, and
storage time conditions.
Table 2-5 Storage Parameters
Indoor, clean (without dust)
-40°C (-40F) to 70°C(158F)
Total transportation and storage time should not exceed six months. Otherwise, the
performance needs to be re-calibrated
2.8 Weight Bearing Capacity
The CRD10 unit is installed on the floor of the computer room, Therefore, the weight bearing capacity of the
floor of the computer room must be taken into consideration.
If the weight bearing capacity cannot be estimated, consult Vertiv or the customer service/support center.