Chapter 6: Specifications
Table 6-1 UPS Specifications
CAPACITY 1000 VA/ 900 W 1500 VA/ 1350 W 2000 VA/ 1800 W 3000 VA/ 2700 W
GXTRT- 1000IRT2UXL 1500IRT2UXL 2000IRT2UXL 3000IRT2UXL
INPUT
Voltage
Range
Low Line Transfer
180 VAC / 160 VAC / 140 VAC / 120 VAC ± 5%
(Ambient Temp. < 35 °C)
(Based on load percentage 100% - 80% / 80% - 70% / 70% - 60% / 60% - 0%)
Low Line Comeback
195 VAC / 175 VAC / 155 VAC / 135 VAC ± 5 %
(Ambient Temp. < 35 °C)
(Based on load percentage 100% - 80% / 80% - 70% / 70% - 60% / 60% - 0%)
High Line Transfer 300 VAC ± 5 %
High Line Comeback 290 VAC ± 5 %
Frequency Range 40 Hz ~ 70 Hz
Phase Single phase with ground
Power Factor 0.95 @ nominal input voltage
OUTPUT
Output Voltage 220/230/240 VAC
Output Power Factor 0.9
AC Voltage Regulation ± 1% (Batt. Mode)
Frequency Range 47 ~ 53 Hz or 57 ~ 63 Hz (Synchronized Range)
Frequency Range (Batt. Mode) 50 Hz ± 0.5% or 60 Hz ± 0.5%
Overload in Online Mode
Ambient Temp. < 35 °C:
< 105%: Operate continuously
105% - 110%: Transfer to bypass after 10 minutes
110% - 130%: Transfer to bypass after 1 minute
> 130%: Transfer to bypass after 3 seconds
Ambient Temp. > 35 °C:
Derate above times 50%
Overload in Battery Mode
Ambient Temp. < 35 °C:
< 105%: Operate continuously
105% - 110%: UPS shuts down after 10 minutes
110% - 130%: UPS shuts down after 1 minute
> 130%: UPS shuts down after 3 seconds
Ambient Temp. > 35 °C:
Derate above times 50%
Overload in bypass Mode
< 110%: Operate continuously
110% - 120%: UPS shuts down after 30 minutes
120% - 130%: UPS shuts down after 10 minutes
130% - 150%: UPS shuts down after 1 minute
> 150%: UPS shuts down immediately
Transfer
Time
AC Mode to Batt. Mode Zero
Inverter to Bypass 4 ms (Typical)
Waveform Pure Sinewave
EFFICIENCY
Online Mode 88% 88% 89% 90%
Battery Mode 83% 84% 87% 88%

Other manuals for Vertiv LIEBERT GXT RT Series

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Vertiv LIEBERT GXT RT Series and is the answer not in the manual?

Vertiv LIEBERT GXT RT Series Specifications

General IconGeneral
BrandVertiv
ModelLIEBERT GXT RT Series
CategoryUPS
LanguageEnglish

Related product manuals