MODEL NUMBER GXT4-1500RT120 GXT4-2000RT120 GXT4-3000RT120 GXT4-3000RT208
RATING 1500VA/1350W 2000VA/1800W 3000VA/2700W 3000VA/2700W
Frequency 40 - 70Hz; Auto Sensing
Input Power Cord
10 ft. attached w/
NEMA 5-15P plug
10 ft. attached w/
NEMA L5-20P
plug
10 ft. attached w/
NEMA L5-30P
plug
10 ft. attached w/
NEMA L6-20P plug
Output AC
Output Receptacles 5-15R × 6
L5-20Rx1+ 5-20R
× 6
L5-30R × 1 +
5-20R × 6
L6-20R × 1 + L6-
15R×2
Voltage 110/115/120VAC (user-configurable); ±3%
208/220/230/240
VAC
(user-configurable);
±3%
Waveform Sine wave
Utility (AC) Mode Overload
200% for 2 seconds
150% for 50 seconds
200% for 2 seconds
150% for 10 seconds
Battery
Type Valve-regulated, non-spillable, lead acid
Qty × V × Rating 4 × 12V × 9.0Ah 6 × 12V × 9.0Ah
Battery Mfr./Part # Panasonic/UP- RW1245; CSB/HR 1234W F2; CSB UPS12460F2
Backup Time See Battery run times (continued) on page60
Recharge Time to 90% capacity after full
discharge
with 100% load till UPS auto-shutdown
(Internal Batteries Only)
6 Hours 5 Hours
Environmental
Operating Temperature, °F (°C) +32 to +104 (0 to 40); see Operating Temperature Parameters on page57
Storage Temperature, °F (°C) 5 to +122 (-15 to 50)
Relative Humidity 0% to 95%, non-condensing
Operating Elevation Up to 10,000 ft. (3000 m) at 77ºF (2C) without derating
Storage Elevation 50,000 ft. (15000 m) maximum
Audible Noise
< 45dBA at 3ft (1m)
rear
< 46 dBA at 3ft. (1m)
front and side
<48dBA max @ 3ft (1m) front and side
<48dBA max @ 3ft. (1m) rear
Agency
Safety UL 1778, c-UL Listed
Table 9.2 Specifications forGXT4-1500RT120 to GXT4-3000RT120 and GXT4-3000RT208 (continued)
9 Specifications
55