NUMBER OF
EXTERNAL
BATTERY
CABINETS
LOAD
PERCENT
OF
CAPACITY
120 VAC RTMODELS
208VAC
RTMODELS
500VA 700VA 1000VA 1500VA 2000VA 3000VA 3000VA
Internal Battery
+ 1 External
Battery Cabinet
10% 684 584 418 385 288 276 261
20% 419 319 224 202 151 148 143
30% 284 220 159 137 100 99 94
40% 226 171 119 101 73 73 70
50% 186 138 92 79 54 54 53
60% 158 113 73 61 42 43 42
70% 136 94 60 50 35 36 35
80% 118 80 51 42 28 29 29
90% 103 68 44 37 24 25 24
100% 92 59 37 31 20 21 21
Internal Battery
+ 2 External
Battery Cabinets
10% 1319 1122 798 670 505 484 460
20% 799 616 433 353 262 257 246
30% 560 423 299 234 175 174 167
40% 436 323 224 176 129 129 126
50% 354 259 179 139 101 102 100
60% 298 216 148 114 82 83 81
70% 256 183 124 95 67 69 67
80% 223 158 107 82 55 57 56
90% 199 139 92 70 47 48 47
100% 178 123 82 59 41 42 41
Table 9.5 Battery run times (continued)