Vertiv | Liebert® GXT5 | Installer/User Guide 79
Table 7-2 UPS Specifications, 3KL620, 3KL630, and 6KL630 models
MODEL GXT5- 3KL620RT2UXL 3KL630RT2UXL 6KL630RT2UXL
RATING
3000 VA/2700 W 3000 VA/3000 W 4900 VA/4900 W
28% ~ 70% loading 129~ 164VAC/288VAC
175 – 280 VAC
0% ~ 28% loading 129VAC/288VAC
Frequency 40 Hz ~ 70 Hz; auto-sensing
Input Power Cord L6-20P L6-30P L6-30P Plug (on PD5-L630 POD)
Output AC
Output Receptacles 2x L6-20R & 2x L6-15R 2x L6-30R & 2x L6-15R
(2) L6-20R and (2) L6-30R
on 12-in� (300-mm) cords (on PD5-
L630POD)
Voltage 208VAC ±3%
Waveform Sine wave
Normal Mode Overload
>200% for 250ms
150- 200% for 2 seconds
125-150% for 10 seconds
105-125% 15 seconds
105% to 125% for 5 minutes
125% to 150% for 60 seconds
>150% (impact load) minimum 200
ms
Internal Charger
Charging Current 2�25 A (default), maximum 8 A 2�25 A (default), maximum 5 A
Battery Parameters
Type Valve-regulated, non-spillable, lead acid
Quantity x Voltage x Rating 6 × 12V × 90Ah 16 x 12V x 90AH
Battery Mfr�/Part # LEOCH DJW12-90
Back-up time See Battery Run Times on page 81
Recharge time 3 Hours to 90% capacity after full discharge into 100% load
5 hours to 90% capacity after full-
discharge into 100% load
Environmental
Operating Temperature, °F (°C)
32 to 122 (0 to 50); Operating temperature may be increased to
122°F (50°C) with a 10% de-rating of the output power
32 to 104 (0 to 40) (no derating)
Storage Temperature, °F (°C) –4 to 140 (–20 to 60) [batteries are from 5 to 104 (–15 to 40)]
Relative Humidity 0% – 95% non-condensing
Operating Elevation Up to 10,000 ft (3,000 m) at 77°F (25°C) without derating
Audible Noise
<48 dBA max� at 3 ft (1 m) front and sides, <48 dBA max� at 3 ft (1 m)
rear
<50 dBA,at 3�2 ft (1 m) from the
front and sides,
<55 dBA, at 3�2 ft (1 m) from rear
Agency
Safety
EN 62040-1:2008+A1:2013
GS mark
UL 1778 5th Edition and CSA 22�2 No� 107�1
UL1778, c-UL listed
EMC
EN 62040-2:2006
EN 61000-3-2:2014
EN 61000-3-3:2013
EN61000-4-2
EN61000-4-3
EN61000-4-4
Transportation ISTA Procedure 1A ISTA Procedure 1E
Surge Immunity
ANSI C62�41 Category B (6kV/3kA)
IEC 61000-4-5
RFI/EMI CISPR22 Class A FCC Part 15 (Class A)

Table of Contents

Other manuals for Vertiv Liebert GXT5-2000LVRT2UXL

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Vertiv Liebert GXT5-2000LVRT2UXL and is the answer not in the manual?

Vertiv Liebert GXT5-2000LVRT2UXL Specifications

General IconGeneral
BrandVertiv
ModelLiebert GXT5-2000LVRT2UXL
CategoryUPS
LanguageEnglish

Related product manuals