Evaporator Model MMD35E or MMD35K
Condensing Unit Type
PFH - Outdoor MCD - Indoor
External Static Pressure, in. wg. (mm) N/A 0.50 (13)
Unit Refrigerant Charge, oz. (kg) 213 (6.0) 213 (6.0)
Unit Operating Weight, lb. (kg) 241 (109) 240 (109)
Free-Cooling Coil Option Net Capacity Data - kW (Btuh) using 4F EWT
80°F DB, 62.8°F WB (26.C DB,
17.1°C WB) 38%RH
Total 9.50 (32,400)
Sensible 9.05 (30,800)
75°F DB, 61°F WB (23.9°C DB,
16.1°C WB) 45%RH
Total 8.20 (28,000)
Sensible 7.60 (25,900)
72°F DB, 60°F WB (22.2°C DB,
15.5°C WB) 50%RH
Total 7.45 (25,400)
Sensible 6.70 (22,900)
Flow Rate - GPM (l/m) 5.9 (22.4)
Pressure Drop - ft. water (kPa) 9.1 (27.2)
Free-Cooling Coil - Copper Tube/Aluminum Fin
Face Area ft
2
(m
2
) 3.1 (0.28)
Coil Rows 3
Max Face Velocity-fpm (m/s) 394 (2.0)
Internal Fluid Volume - gal (l) 2.0 (7.6)
Water supply and return connections, in (mm) OD 7/8 (22.2)
The net capacity data has fan motor heat factored in for all ratings and the entering air conditions of 75°F (23.9°C), 45%RH, is the standard rating
condition for ASHRAE 127-2007. All capacities are nominal values; actual performance will be ±5%.
Table 6.2 Air-cooled data, 50Hz (continued)
Vertiv | Liebert Mini-Mate22 and 3 ton Technical Data Manual | 20