220 - 1 Ph - 50Hz 380/415 - 3 Ph - 50Hz
Base Evaporator Model Number MM*35E MM*35E
Condensing Unit Model Number MC*37W MC*37W
FLA 26.3 11.5
with Electric Reheat and Humidifier
FLA 44.9 17.5
with SCR Reheat and Humidifier
2
FLA 68.0 25.4
* Specify disconnect or no disconnect
Notes:
1. Use MM*35E for MM*35K, except with SCR reheat.
2. SCR Reheat not available with MM*35K.
Table 9.13 Electrical data, 50Hz water/glycol-cooled sys-
tems using single-point power kit, evaporator with direct-
drive blowers and indoor condensing unit (continued)
220 - 1 Ph - 50Hz 380/415 - 3 Ph - 50Hz
Base Evaporator Model Number MM*35E MM*35E
Condensing Unit Model Number MC*37W MC*37W
Cooling Only
FLA 24.1 9.0
with Electric Reheat
FLA 49.1 18.7
with SCR Reheat
3
FLA 65.8 22.9
with Humidifier
FLA 30.5 12.7
with Electric Reheat and Humidifier
FLA 49.1 18.7
with SCR Reheat and Humidifier
3
FLA 72.2 26.6
* Specify disconnect or no disconnect
Notes:
1. Belt drive data includes externally mounted high static blower box, powered from
evaporator unit.
2. Use MM*35E for MM*35K, except with SCR reheat.
3. SCR Reheat not available with MM*35K.
Table 9.14 Electrical data, 50Hz water/glycol-cooled systems using
single-point power kit, evaporator with belt-drive blowers and indoor
condensing unit
Vertiv | Liebert Mini-Mate22 and 3 ton Technical Data Manual | 57