VESDA-EVES-A00-P Product Guide
110 www.xtralis.com
Sector 4:
Fire 2
Fire 1
Action
Alert
First Alarm
Fire 1 relay connection from Remote Display/Relay to fire
panel tested (using the Xtralis VSC Alarm Test Command
for the detector).
Urgent Fault relay connection from Remote
Display/Relay to fire panel tested (using the Xtralis VSC
Alarm Test Command for the detector).
Minor Fault Relay connection to Fire Panel verified using
the Xtralis VSC Fault Test command for the detector
Disable/Standby Relay connection to Fire Panel Verified.
Scanning relay connection to Fire Panel verified.
Client Representative Name
Test witnessed by:
Date:
Hand Over Documents
Copy of this form
ASPIRE Installation Data Pack
ASPIRE Bill of Materials
Configuration printout from Xtralis VSC for each
detector
Configuration printout from Xtralis VSC for each display
module
Smoke test results
Forms required for compliance with local codes and
standards
Customer's Signature
Date:
Commissioner's Signature
Date: