EasyManua.ls Logo

Viconics VT8000 - Page 25

Viconics VT8000
82 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
028 -0427-15 _UI-V T8350_ A4 _ EN www.viconics.com June 2020
25
VT8350 [ User Interface Guide ]
MODBUS NETWORK SETTINGS
Modbus network screen shows when Modbus is selected in wired protocol parameter.
PARAMETER DETAILS
Conguration Parameters Default Value Signicance and Adjustments
COM address
Default value: 254
Communication Address
Valid address range is set at 1 to 247 and each Modbus device must have a
unique address. Other values not recommended for Modbus.
Default value of 254 disables Modbus communication for the Room Controller.
Range: 0 to 254
Network units
Default value: SI
Measurement Units
Network units transmitted over the BACnet network.
NOTE: Use the Temperature scale parameter to change the display units locally
on the Room Controller.
Imperial: network units shown as Imperial units.
SI: network units shown as International Metric units.
Choices: Imperial or SI
Baud rate
Default value: 19200
Modbus Baud Rate
Automatically detects Modbus baud rate.
Choices: 57600, 38400, 19200, 9600 and 4800
Parity
Default value: Even
Parity
Determines how the parity bit of the character’s data frame is set to detect any
errors in the sent/receives frame.
Choices: None, Odd and Even
Modbus Network
Parity
None
Network units
SI
Baud rate
19200
COM address
254