028 -0427-15 _UI-V T8350_ A4 _ EN www.viconics.com June 2020
46
VT8350 [ User Interface Guide ]
Setpoints Screens
SETPOINTS 1/2
PARAMETER DETAILS
Conguration Parameters Default Value Signicance and Adjustments
Unocc. cool
Default value: 80°F (27°C)
Unoccupied Cool Setpoint
Cooling Temperature setpoint used by the Room Controller when in
Unoccupied mode.
Range: 54 to 100°F (12.0 to 37.5°C)
Standby cool.
Default value: 78°F (25.5°C)
Standby Cooling Setpoint
Cooling Temperature setpoint used by the Room Controller when in
Standby mode.
Range: 54 to 100°F (12.0 to 37.5°C)
Occ. cool
Default value: 75°F (24°C)
Occupied Cool Setpoint
Cooling Temperature setpoint used by the Room Controller when in
Occupied or Override mode.
Range: 54 to 100°F (12.0 to 37.5°C)
Occ. heat.
Default value: 72°F (22°C)
Occupied Heating Setpoint
Heating Temperature setpoint used by the Room Controller when in
Occupied or Override mode.
Range: 40 to 90°F (4.5 to 32.0°C)
Standby heat.
Default value: 69°F (20.5°C)
Standby Heating Setpoint
Heating Temperature setpoint used by the Room Controller when in
Standby mode.
Range: 40 to 90°F (4.5 to 32.0°C)
Unocc. heat.
Default value: 62°F (17°C)
Unoccupied Heating Setpoint
Heating Temperature setpoint used by the Room Controller when in
Unoccupied mode.
Range: 40 to 90°F (4.5 to 32.0°C)
1/2 Setpoints
Occ. cool
Standby cool
Unocc. cool
25.5 °C
24.0 °C
22.0 °C
20.5 °C
16.5 °C
26.5 °C
Occ. heat
Standby heat
Unocc. heat