028 -0427-15 _UI-V T8350_ A4 _ EN www.viconics.com June 2020
82
VT8350 [ User Interface Guide ]
Appendix A: Terminal Correspondence
The terminals of a VT8350 are identied differently and have a wider range of possible functions compared to those of any of the
VT7300 series Room Controllers. Nonetheless, there is a direct correspondence of functions between the terminals of the VT7300
series and the VT8350 series. Consult the table below to verify the appropriate terminal when replacing a VT7300 Room Controller
with a VT8350 Room Controller.
VT7300 VT8350
Terminal name Terminal ID Terminal name Terminal ID
Binary Input 1 BI1 Universal Input 16 UI16
Binary Input 2 BI2 Universal Input 17 UI17
Universal Input 3 UI3 Universal Input 19 UI19
Sensor Common Scom Terminal 18 Common COM
Remote Sensor RS Universal Input 20 UI20 - RS
Sensor Common Scom Terminal 21 Common COM
Mix/Supply Sensor MS Universal Input 22 UI22 - SS