I-768N / Series 768N FireLock NXT
Dry Valve / Installation, Maintenance, and Testing Manual
Auto Vent
Sleeve of
Series 776
Low-Pressure
Actuator
(Step 5)
Alarm Test
Ball Valve
(Step 3)
INITIAL SYSTEM SETUP
Step 1:
Confirm that all system drains are shut and that the system is free of
leaks.
Step 2:
Confirm that the system has been depressurized. The gauges should
indicate zero pressure.
Step 2a: If a Series 746-LPA Dry Accelerator is installed, confirm
that the isolation ball valve is closed.
Step 2b: If a Series 746-LPA Dry Accelerator is installed, open
the ¼-turn vent ball valve.
Step 3:
Confirm that the alarm test ball valve is closed.
Step 4:
Charge the system with air by turning on the compressor or by
opening the fast-fill ball valve on the AMTA. Charge the system to
13 psi/90 kPa/0.9 Bar minimum. Refer to the “Air Supply Requirements”
section.
Step 5:
When the system reaches approximately 10 psi/69 kPa/0.7 Bar, and no
additional moisture is being released from the Auto Vent, pull up on the
Auto Vent Sleeve of the Series 776 Low-Pressure Actuator. NOTE: The
Auto Vent Screw should seal and remain in the set (“UP”) position.
Step 6:
When system air pressure is established, close the fast-fill ball valve on
the AMTA.
Step 7:
Open the slow-fill ball valve on the AMTA. NOTE: Failure to leave the
slow-fill ball valve open may allow system pressure to drop, resulting in
valve operation in the event of a system leak.
I-768N_11REV_C

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Victaulic 768N FireLock NXT Series and is the answer not in the manual?

Victaulic 768N FireLock NXT Series Specifications

General IconGeneral
BrandVictaulic
Model768N FireLock NXT Series
CategoryControl Unit
LanguageEnglish

Related product manuals