5.5 Configuration with DIP switches
A number of settings can be changed using DIP switches (see appendix A, position
M).
This is done as follows:
Turn the MultiPlus on, preferably without load en without AC voltage on the input. The
MultiPlus will then operate in inverter mode.
Step 1: Setting the DIP switches for:
- the required current limitation of the AC input.
- AES (Automatic Economy Switch)
- maximum charge current.
- selection of stand-alone, parallel or 3-phase operation.
To store the settings after the required values have been set: press the 'Up' button for
2 seconds (upper button to the right of the DIP switches, see appendix A, position J).
The DIP switches can now be used to apply the remaining settings (step 2).
Step 2: other settings
To store the settings after the required values have been set: press the 'Down' button
for 2 seconds (lower button to the right of the DIP switches). The DIP switches can be
left in the selected positions, so that the ’other settings’ can always be recovered.
Remarks:
- The DIP switch functions are described in 'top to bottom' order. Since the uppermost
DIP switch has the highest number (8), descriptions start with the switch numbered 8.
- In parallel mode or 3-phase mode, not all devices require all settings to be made
(see section 5.5.1.4).
For parallel or 3-phase mode, read the whole setting procedure and make a note of
the required DIP switch settings before actually implementing them.