GB
General notice (liability): the details of this technical documents serve for description. Consents regarding the availability of certain features or
regarding a certain purpose always require a special written agreement.
Page 14 GB 7.2.6 Right reserved to make technical changes!
7.2.6 Operator access
The parameters P02 .. P23 can only be accessed if the password 5 is entered in parameter P01 or if the password for the
operations parameters has been selected.
The parameters shown in italics cannot be changed.
Display reading of the selected parameter during entry of parameters
Function Parameter German English French Unit Range
Password P01 P01 P01 P01 0-99
Temperature setting P02 SL.t. n.t. t.n. °C P31..P32
Defrost cycle (h) P03 Ab.h dE.C c.dE hours 1-24
Defrost time (Min) P04 Ab.d dE.t d.dE minutes 5-60
Humidity (Evaporator fan)
LO=Operating Time with compressor
(low relative humidity)
HI=Constant Running (High relative humidity)
P05 r.F. HU. HU.
Language
d = German
e = English
f = French
P06 P06 P06 P06
Control lock
0 = Locked
1 = Released
P07 tA.F bo.E bo.E 0-1
Display of evaporator temp P08 P08 P08 P08 °C -50 .. 50/OFF
Display of condenser temp P09 P09 P09 P09 °C 0 .. 99/OFF
The following parameters can only be shown if the value x3 is set in P30 and a DCF signal
receiver is connected.
Current time (h) P10 P10 P10 P10 Std. 0 .. 23
Current time (Min) P11 P11 P11 P11 Min. 0 .. 59
Defrosting Time 1 P12 t.01 t.01 t.01 hh.m(x10) 00.0 ..23.5
Defrosting Time 2 P13 t.02 t.02 t.02 hh.m(x10) 00.0 ..23.5
Defrosting Time 3 P14 t.03 t.03 t.03 hh.m(x10) 00.0 ..23.5
Defrosting Time 4 P15 t.04 t.04 t.04 hh.m(x10) 00.0 ..23.5
Defrosting Time 5 P16 t.05 t.05 t.05 hh.m(x10) 00.0 ..23.5
Defrosting Time 6 P17 t.06 t.06 t.06 hh.m(x10) 00.0 ..23.5
Defrosting Time 7 P18 t.07 t.07 t.07 hh.m(x10) 00.0 ..23.5
Defrosting Time 8 P19 t.08 t.08 t.08 hh.m(x10) 00.0 ..23.5
Defrosting Time 9 P20 t.09 t.09 t.09 hh.m(x10) 00.0 ..23.5
Defrosting Time 10 P21 t.10 t.10 t.10 hh.m(x10) 00.0 ..23.5
Defrosting Time 11 P22 t.11 t.11 t.11 hh.m(x10) 00.0 ..23.5
Defrosting Time 12 P23 t.12 t.12 t.12 hh.m(x10) 00.0 ..23.5
Access for Specialist Firms
Access to P29 and above is only possible if the password for the operational parameters is entered in P01
(see special parameters list)
EIf no button is pushed within ten seconds, parameter entry is ended, and coldroom temperature will be displayed. The yellow LED in
the button „Stop-Start-Enter“ goes out, and this button resumes the function „Stop-Start“ Using some parameters, the functions of the
regulator can be monitored constantly. In this case, the yellow LED in the button „Stop-Start-Enter“ will blink. By activating the button
„Stop-Start-Enter“, the LED will operate for 10 seconds, and the button will subsequently return to normal operation.