8. Types of operational parameters
8.1 Parameter list
Attention!
The following parameters are important for the operation of the refrigeration unit. They may only be changed by
specialists. It is therefore recommended that the password for the access to the parameters be kept secret.
If the parameters are changed, the new ones should be entered in the column „Changed Values“.
Parameter for mode of operating (enabling by codeword P01 = 22)
The following parameters are as parameter for mode of operating for cooler resp. freezer prepared.
They can be adjust. If neccessary they can restore through P 50 and P 51 to the factory setting (see 7.5.2.3).
Parameter Description Unit Range
Changed
values
Recommended
Normal
cooling
Deep-
freezer
P28 Signal Display from DCF Antenna seconds 0-59
P29 Door contact switch (0=without/1=with) 0-1 0 0
P30
Defrosting
00-03;
10-13
00
x0=according to set cycle times
x1 = according to set cycle times, but dependent on running time
of compressor
x2=dependent on set switch-on times (only with DCF Antenna)
x3=defrosting as required
0y=“Defrost Start“, door contact switched off
1y=“Defrost Start“, door contact switched on
P31 Max allowable room temperature °C -50 .. +50 20 -5
P32 Min allowable room temperature °C -50 .. +50 -5 -25
P33 Room temperature differential K 1-8 2 2
P34 Minimum stop time, compressor minutes 3-10 3 3
P35 Initiation delay, evaporation fan minutes 0-10 3 3
P36 Running time after stop, evaporator fan minutes 0-20 0 0
P37
Running time after stop, evaporator fan, to determine degree
of icing
minutes 0-10 3 3
P38 Temperature difference to allow switch-on of defrosting K 10-40 25 25
P39 Defrost temperature limit °C +5 .. +50 20 20
P40 Drainage time, evaporator minutes 0-10 3 3
P41 Start temperature, evaporator fan °C -20 .. +10 -5 -15
P42 Delay time, temperature alarm minutes 0-99 60 60
P43 Upper temperature alarm (Setting + P43) K 0-20 10 10
P44 Lower temperature alarm (Setting – P44) K 0-20 5 5
P45 Delay time, door contact alarm minutes 0-99 4 4
P46 Temperature setting , condenser for rotation speed regulator °C 0-50 20 20
P47 Rotation speed, condenser fan in %
OFF/
10..100
P48 Min rotation speed, condenser fan in % 10 .. 100 40 40
P49 Conductivity, rotation speed regulator, condenser fan 1-100 10 10
P50 Unit type, 1=normal refrigeration, 2=Deepfreezer 1-2 1 2
P51 Revert to plant settings (P=78)