Submenu 1 Submenu 2 Values
Presetting
Description
CS Cooler FS Freezer
Drain down
time
0 min to 10 min 3 min 3 min
After the defrosting process, a
waiting time is applied until the
normal operating mode (cool-
ing) is returned. In the case of
hot gas defrosting, the compres-
sor downtime runs concurrently.
I. e. the cooling operation can
only start after elapsing of this
time.
Drain line
heater acti-
vation pre
defrost
Drain pre heat
0 minto 10 min 3 min 3 min
Lead time for the drain line.
Starts prior to the start of the
defrosting process. Thus, the
defrosting water does not drip
on the cold dripping tray and in
the cold drain hose.
Freezing
temperature
Yes / No Yes Yes
Displays the temperature before
defrosting began in the data
logger during defrosting and
prevents temperature peaks
during defrosting.
Back
Fan
Fan type
Standard
Eco-Linear
– Activation of the fan with 230
V and the control output 0-10
V linear.
– Activation with a straight line
through the defined points
temperature 5 / speed 5 (lower
point) and temperature 1 /
speed 1 (upper point).
Pr. Evap. 0 min to 10 min 3 3
Delays the start-up of the evapo-
rator fan together with the start
temperature of the evaporator
fan.
Sub. Evap. 0 min to 10 min 0 0
Uses the residual cold from the
evaporator.
Start Evap. -20°C to 10°C +5°C -15°C
Delays the start of the evapo-
rator fan after defrosting or a
restart together with the delay
time.
Temp Step 1
Min. value v.
temp. intervals
of 5 to max. 50°C
+35°C +35°C
Upper temperature point for
speed regulation. (See figure)
Temp Step 5
min. 0°C to max.
value v. temp 5
00
Lower temperature point for
speed regulation. (See figure)
Rotary speed 1
min. value v
rotary speed 5 to
max 100%
80 80
Upper percentage for speed
regulation. (See figure)
Rotary speed 5
min. 0% to max.
value v. rotary
speed 5
00
Lower percentage for speed
regulation. (See figure)
Back
1
5
5
1
max. 100%
Temperature
Rotary speed