Coding
Burner switching hysteresis
Switching hysteresis 4 K (04:0)
Heat−demand dependent switching hysteresis (only with outside temp. sensor)
ERB50 function (04:1)
Subject to heat demand, values between 6 and 12 K result.
ERB80 function (04:2)
Subject to heat demand, values between 6 and 20 K result.
The heat demand−dependent switching hysteresis, therefore, takes the boiler
load into account.
The switching hysteresis, i.e. the burner operating time, is varied subject to
the current heat demand.
5862730GB
Burner
+2
ON
OFF
−2
low
heat demand
average
heat demand
high
heat demand
Time
set
low
heat demand
average
heat demand
high
heat demand
Time
Burner
ON
OFF
+9
−3
set
+3
low
heat demand
average
heat demand
high
heat demand
Time
Burner
ON
OFF
+17
−3
set
+3