Heating system designs
System version 15 (cont.)
Possible applications
The cascade and cylinder control
must be provided by a higher control
unit.
The Vitocrossal 300 (lead boiler) and
the next low temperature boiler
should be operated via a
weather−compensated control
system with modulating boiler water
temperature and load−dependent
sequential control  two−stage or
modulating burners are regulated.
Vitocrossal 300 is equipped with two
return connectors. The heating
circuits with the higher return
temperature are connected to the
upper return connector and those
with lower return temperatures to
the lower return connector. Note:
connect at least 15% of the rated
output to the lower return connector.
The return temperature raising
facility is available as an accessory
or must be provided on site.
Raise the return temperature
through a shunt−pump and by
closing the butterfly valve.
Temperature sensor T1 controls the
butterfly valve. Temperature sensor
T2 switches the shunt pump.
5862730GB

Table of Contents

Other manuals for Viessmann GC1

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Viessmann GC1 and is the answer not in the manual?

Viessmann GC1 Specifications

General IconGeneral
BrandViessmann
ModelGC1
CategoryControl Unit
LanguageEnglish

Related product manuals