LED Meaning Cause Remedy
Illuminated green Circulation pump in
operation
Flashes green in
short intervals
Circulation pump in
standby
Fault indications
Flashes red and
green alternately
Circulation pump is
ready for operation
but not running.
Note
The circulation
pump starts auto-
matically after the
cause of the fault
has been re-
moved.
Undervoltage
(< 160 V~)
Overvoltage
(> 253 V~)
Check the power
supply. (195 V~ < U
< 253 V~)
Motor temperature
too high
Check ambient and
heat transfer medi-
um temperatures.
Flashes red Circulation pump
switched off
(blocked)
Circulation pump
does not start auto-
matically.
Replace circulation
pump (see
page 11)
LED off No operating volt-
age.
Check connecting
cable.
LED faulty Check whether the
circulation pump is
running.
PCB faulty Replace the circula-
tion pump (see
page 11).
LED on the HE circulation pump
5773 841 GB