Solar pump assembly to the right of
the Solar-Divicon
Solar pump assembly to the left of the
Solar-Divicon
Fitting the Solar-Divicon
■ The Solar-Divicon and the solar pump
assembly are unsuitable for direct con-
tact with swimming pool water.
■ Every time the system is drained, flush
the system with heat transfer medium.
■ A tee connection is available for the
purpose of connecting the expansion
vessel and the stagnation heat sink in
the flow.
■ Install a thermal insulation loop if the
expansion vessel is installed higher
than the Solar-Divicon.
■ Use only bronze, brass or stainless
steel fittings, copper or stainless steel
pipes or Viessmann stainless steel
solar circuit pipes for the installation.
Use hemp only in conjunction with
pressure and temperature-resistant
sealants.
■ Check the sealing faces for cleanli-
ness and damage before assembly.
■ The discharge pipe must exit into an
open container.