External blocking
The "External blocking" function is
connected via the external extension
input "aVD".
In coding address "32", you can select
the influence the "Ext. blocking" sig-
nal should have on the connected cir-
culation pumps.
External demand
The "External demand" function is
connected via the external extension
input "aVD".
In coding address "34", you can select
the influence the "Ext. demand" signal
should have on the connected circula-
tion pumps.
The minimum set boiler water tem-
perature in case of external demand
is selected in coding address "9b".
Venting program
During the venting program, the circu-
lation pump will be alternately
switched ON and OFF for 30 s respec-
tively over a period of 20 min.
For a certain period, the diverter valve
is alternately set towards heating and
DHW heating. The burner is switched
OFF during the venting program.
The venting program is activated via
coding address "2F:1". The program
is automatically disabled after 20 min,
and coding address "2F" is set to "0".
Filling program
In the delivered condition, the diverter
valve is set to its central position,
enabling the system to be filled com-
pletely. After switching ON the control
unit, the diverter valve no longer goes
into its central position.
Afterwards, the diverter valve can be
moved via coding address "2F:2" into
the central position. In this position,
the control unit can be switched OFF,
and the system can be filled comple-
tely.
Control functions (cont.)
105
Function description